Tuesday 19 August 2014

Import Validation Tool


The tool can be downloaded from here
The Excel template can be downloaded from here
The layout of the tool can be seen as follows:
Capture
This tool includes features listed below:
  • Validation of Materials and Formulas in CSV files.
  • Automated validation of Materials and Formulas in Excel files.
  • Detailed error description of invalid records.
  • Generate blank Material and Formula template.
  • Export valid data to CSV files from Excel files.
The list of error messages are listed below:
  • Code missing or too long (maximum 25 characters)
  • Name missing or too long (maximum 50 characters)
  • Missing materials from formulas

Validate from CSV

Press ‘Choose File’ button and choose the CSV file you want to validate. First choose a Material file and the records will be automatically registered. If the materials are not valid then error messages will be displayed. If the materials are all valid then continue the operation pressing the ‘Choose File’ button again to choose the Formula file.
Valid records are displayed in the table ‘Valid Records’ and invalid records are displayed in the table ‘Invalid Records’. When going through the rows of Invalid Record table, you will be able to see the detailed error description underneath the same.
Capture2
Capture1

Validate from Excel

Click ‘Choose File’ button and choose the Excel file. This will check if all the records are valid. Valid records are displayed in the table ‘Valid Records’ and Invalid records are displayed in the table ‘Invalid Records’. When an invalid record is selected from the table, you will be able to see the detailed error description below the table.
When all the records are valid, it will ask you to save the Materials and Formulas to a CSV file. Press save to save them in your preferred directory.
Capture5
Capture6

Generate File

If you want to create a CSV file with the Materials and Formula file template, click ‘Generate File’ button and save them in your preferred directory.

Thursday 14 August 2014

Setting Dispense Parameters for a Material

 

When a material is attached to a dispense valve, the tolerance and pump settings associated with that valve are used to control the dispense performance.

The pump settings are HIGH and LOW pressure. HIGH pressure controls the pump speed in full flow and LOW pressure controls the pump speed in low flow and during spitting. If the HIGH setting is too high the dispenser may over dispense. If the setting is too low, the pump may stall and fail to pump any material.

Generally the HIGH setting should be greater than the LOW setting unless advised by a Rexson engineer.

The tolerance settings are UNDER, ALARM and %. % tolerance comes into effect on dispenses larger than 1 kg. % tolerance works the same for amounts above or below the requested amount and is usually set to 1%.

In smaller dispenses UNDER determines the largest amount that the dispensed amount can deviate below the requested amount and still be in tolerance. ALARM determines the largest amount that the dispensed amount can deviate above the requested amount and still be in tolerance. On a water based ink system, these settings are usually the same at 0.005 kg for colours and 0.020 kg for non-colour products. Some strong colours may require smaller tolerances of 0.002 kg.

If the UNDER tolerance is set to 0.020 kg, any request for less than 0.020 kg of material will be seen as in tolerance, so no material is dispensed. This is the correct behaviour for absolute tolerances.

To set the tolerances and pressures you will need a supervisor (level 3) or engineer/master (level 4) RFID key.

From the Main Menu go to Configuration

 

image

then Operations

image

From here you can view the settings for each dispense valve

image

Using the arrow buttons on the bottom right of the screen, select the valve number for the material you wish to adjust. The material name and code will be displayed next to the valve number.

Press the Pump/Tank button to change pump pressures.

image

After making changes press the Save button to save the settings and write them to the controller.

Press the Tolerance button to change tolerances

image

After making changes press the Save button to save the settings and write them to the controller.